The Wilkins 2-ZW209 is a pilot operated pressure reducing valve designed to reduce high inlet pressures to safe and stable outlet pressure in commercial and industrial water systems.
Key Specifications:
Other Related Variants:
Materials:
The Zurn 2-ZW209 is recommended for horizontal installation with the valve cover up. Inlet and outlet shut-off valves should be installed for isolation during maintenance. The valve includes standard inlet and outlet pressure gauges, isolation valves, and a wye type strainer for optimal performance and easy serviceability.
ANSI/AWWA C530; NSF/ANSI/CAN 61 (0.25% Maximum Weighted Average Lead Content)
Features & Benefits:
Q: What is the minimum inlet pressure required for the Wilkins 2-ZW209?
A: The minimum inlet pressure is 10 psi higher than the set point or the additional body friction loss at intended flow, whichever is higher.
Q: Can the Zurn 2-ZW209 be installed vertically?
A: The recommended installation orientation is horizontal with the valve cover up. Vertical installation may cause difficulty in properly bleeding air and performing maintenance.
Q: What is the pilot spring adjustment range?
A: The standard pilot is field adjustable from 15 psi to 120 psi. Optional low pressure (5-25 psi) and high pressure (30-300 psi) pilots are available.
NOTICE: Do not use with water that is unsafe or of unknown quality without adequate disinfection either before or after the system.
"Hydrate Everyone, Everywhere!" BottleFillingStations.com | Contact us
Ships within 48 hours · Estimated delivery Jul 18 - Jul 23
US$40
Get nowSign up to your membership to get coupons up to
15%
Get nowOpportunity to enjoy order discount up to 15% off
Top-Converting Item to Boost Your Average Order