Shopping security
The Honeywell FC-SDOL-0424 (Hardware Version V1.2) acts as a high-integrity Safe Digital Output Loop Monitored (LM) module for the Honeywell Fail-Safe Control (FSC) system. This module manages critical final elements, including solenoid valves, actuators, and ESD relays, within a Safety Instrumented System (SIS). It executes fail-safe transitions to a de-energized state upon fault detection or logic commands. We provide this unit as 100% Brand New and Original, ensuring full compliance with SIL 3 safety requirements per IEC 61508.
The FC-SDOL-0424 integrates robust solid-state switching with advanced diagnostic circuitry to maintain loop integrity.
| Specification | Details |
| Channels | 4 Independent Output Channels |
| Output Voltage | 24 V DC |
| Max. Current (Channel) | 1.0 A |
| Max. Total Load | 3.6 A (Thermal Limit) |
| Safety Rating | SIL 3 Capable (IEC 61508) |
| Monitoring | Loop Monitoring (Short circuit, Lead breakage) |
| Max. Inductance | 0.5 H |
| Max. Capacitance | 1 μF |
| Voltage Drop | < 1.3 V @ 1 A |
| Isolation | 500 V AC |
| Dimensions | 4 HP, 3U (Compact Modular Design) |
Comprehensive Loop Diagnostics: The module continuously scans the field loop for short circuits and lead breakages. This monitoring ensures that the safety loop remains ready to execute an Emergency Shutdown (ESD) at all times, preventing "hidden" failures in the wiring.
High Inductive Load Handling: Specifically designed for heavy industrial actuators, the FC-SDOL-0424 manages load inductance up to 0.5 H. This eliminates the need for external suppression components in most standard solenoid applications.
Thermal Self-Protection: The hardware limits the total module load to 3.6 A. This thermal management prevents internal overheating, protecting the module and adjacent I/O cards from heat-induced degradation in high-density cabinets.
Integrated Watchdog (WDG): A dedicated watchdog input monitors processor health. The module only executes output commands when internal system integrity is verified, providing an additional layer of protection against logic errors.
What does "Loop Monitored" mean for the FC-SDOL-0424?
It means the module actively checks the integrity of the field wiring even when the output is off. It detects if a wire breaks or if a short circuit occurs between the module and the final element (e.g., a valve).
Can this module drive 1A on all four channels simultaneously?
While each individual channel supports 1A, the total module load must not exceed 3.6A due to thermal constraints. If you run all four channels, you must balance the load to stay within this safety limit.
Is the FC-SDOL-0424 V1.2 backward compatible with older FSC versions?
Yes, version V1.2 maintains compatibility with standard FSC racks, but you must verify that your system software supports the specific diagnostic features of this hardware revision.
In what condition is this module supplied?
We supply the Honeywell FC-SDOL-0424 as 100% Brand New in original factory packaging. It includes a 12-month warranty and full technical documentation for SIL 3 verification.
Ships within 48 hours · Estimated delivery Jul 12 - Jul 17
US$40
Get nowSign up to your membership to get coupons up to
15%
Get nowOpportunity to enjoy order discount up to 15% off
Top-Converting Item to Boost Your Average Order